UMG 508
(Multifunction Power Analyser)

Overview
Multifunction Power Analyser

The multi-purpose unit for integration into control panels. Continuous monitoring of the power quality, analysis of electrical interference in the event of network problems.

Power Quality
Reliable operation of modern plants and systems always demands a high degree of supply reliability and good power quality. UMG measuring devices reliably record, analyse and document all interferences such as harmonics, unbalance, transients, voltage dips, voltage swells, flickers, phase shifts and reactive power.
Colour Graphic Display
The high resolution graphic display stands for self-explanatory and intuitive operation. Measured values can be illustrated in numeric form, as a bar graph or a line graph. Complex processes such as power quality events or current and voltage can therefore be visualised clearly in waveform.
Ethernet Connection
An Ethernet connection can be used to make integration into an IT network particularly simple and comprehensive. UMG measuring devices with an Ethernet connection run various IP protocols such as TCP/IP, HTTP, FTP, SNMP, DHCP, TFTP, SMTP, BACnet (optional), etc.
Ethernet Modbus Gateway
The Ethernet Modbus gateway can be used to easily include the Modbus RTU devices that are connected to the master device as slaves in an Ethernet architecture. This is also possible via a Modbus RTU interface for devices with identical file formats and matching function codes.
Jasic®
The user can use the graphical programming language Jasic® to add their own functions to a UMG measuring device. Up to seven freely configurable user programs can run in parallel, e.g. monitoring processes or notifications when reaching defined threshold values. In addition to the graphical programming option, the user is also free to program the source code directly in JASIC.
Alarm Management
The alarm management feature in GridVis® monitors all measurement parameters captured by the UMG measuring devices. It comprises escalation management, a logbook function and user management for individual notifications by e-mail, dialogue box on the monitor, etc.In addition to monitoring effective values, short term interruptions and transients, as well as communication with the measuring devices can also be monitored.
Janitza-Netzanalysator-UMG-508-en

Communications
  • Profibus (DP/V0)
  • Modbus (RTU, TCP, Gateway)
  • TCP/IP
  • BACnet (optional)
  • HTTP (Homepage)
  • FTP (File-transfer)
  • SNMP
  • TFTP
  • NTP (time synchronisation)
  • SMTP (email function)
  • DHCP

Interfaces
  • Ethernet
  • Profibus / RS485 (DSUB-9)

PLC Functionality
  • Graphical programming
  • Jasic® programming language
  • Programming of threshold values etc.

Power Quality
  • Harmonics up to 40th harmonic
  • Short-term interruptions (> 20 ms)
  • Transient recorder (> 50 μs)
  • Starting currents (> 20 ms)
  • Unbalance
  • Full wave effective value recording (up to 4.5 min.)

Accuracy of Measurement
  • Energy: Class 0.2 (... / 5 A)
  • Current: 0.2 %
  • Voltage: 0.1 %

Network
  • IT-, TN-, TT-networks
  • 3- and 4-phase networks
  • Up to 4 single-phase networks

Network Visualisation Software
  • GridVis®-Basic (in the scope of supply)

Measured data memory
  • 256 MByte Flash
  • 32 MB SDRAM

Peak demand management (optional)
  • Peak demand management (optional)

8 digital inputs
  • Pulse input
  • Logic input
  • State monitoring
  • HT / LT switching
  • Emax resetting

5 digital outputs
  • Pulse output kWh / kvarh
  • Switch output
  • Threshold value output
  • Emax output
  • Logic output

Areas of Application
  • Continuous monitoring of the power quality
  • Energy management systems (ISO 50001)
  • Master device with Ethernet gateway for subordinate measurement points
  • Visualisation of the energy supply in the LVDB
  • Analysis of electrical disturbances in the event of power quality problems
  • Cost centre analysis
  • Remote monitoring in the property operation
  • Use in test fields (e.g. in universities)

Features

The multi-purpose unit for integration into control panels. Continuous monitoring of the power quality, analysis of electrical interference in the event of network problems.

Power quality
  • Harmonics analysis up to 40th harmonic
  • Acquisition of short-term interruptions
  • Acquisition of transients
  • Display of waveforms (current and voltage)
  • Unbalance
  • Vector diagram
Janitza-UMG 508-GridVis-Graphenset
User-friendly, colour graphical display with intuitive user guidance
  • User-friendly, colour graphical display with intuitive user guidance
  • User-friendly, self-explanatory and intuitive operation
  • Clear and informative representation of online graphs and further power quality events
Fig-Large-colour-display
Modern communications architecture via Ethernet
  • Ethernet interface and web server
  • Faster, better cost-optimised and more reliable communication system
  • High flexibility due to the use of open standards
  • Integration in PLC systems and BMS through additional interfaces
  • BACnet optionally available
Modbus Gateway function
  • Economical connection of devices without Ethernet interface
  • Integration of devices with Modbus-RTU interface possible
  • Data can be scaled and described
  • Minimised number of IP addresses required
Janitza-UMG 508-GridVis-Topologieansicht
Graphical programming
  • Comprehensive programming options (PLC functionality)
  • Jasic® source code programming
  • Sustainable functional expansions far beyond pure measurement
  • Complete APPs from the Janitza library
Powerful alarm management
  • Can be programmed via the graphic programming or Jasic® source code
  • All measured values can be used
  • Can be arbitrarily, mathematically processed
  • Individual forwarding via email sending, switching of digital outputs, writing to Modbus addresses etc.
  • Watchdog APP
  • Further alarm management functions via GridVis®-Service alarm management
Janitza-UMG 508-Alarmmanagement
Dimension Diagrams(in mm)
Janitza-UMG%20508-Massbild-2-Ansichtvonunten
Typical Connections
Janitza-UMG508-Anschlussbild-en